Knowing how to compute the heating requirements is crucial if you want to keep your house toasty warm during the winter. Using the room’s volume as a guide to calculate heating is one of the easiest approaches. This approach calculates the amount of heat required to maintain a comfortable temperature while accounting for the size of the room. Through mastery of this technique, homeowners can efficiently operate their heating systems, guaranteeing comfort and energy economy.
A straightforward rule governs heating calculations based on room volume: the larger the space, the greater the amount of heat required to maintain its temperature. The idea behind this approach is that the volume of a room directly affects how much heat is needed. It’s a basic idea that gives you a good place to start when figuring out how much heat your house actually needs. You can make sure you have the right heating system installed by figuring out the volume of each room.
It’s important to comprehend the factors that affect a room’s heat requirement before beginning the calculation. The quantity and size of windows and doors, insulation, climate, and other elements can all have a big impact on how much heat is required. For example, a room with fewer windows and better insulation will typically need less heating than a room with many windows and poor insulation. You can determine your heating requirements more precisely if you take these variables into account in addition to the room’s volume.
Completing a room’s volume calculation is not too difficult. Measure the room’s length, width, and height in meters to get started. Multiply these measurements together after you have them. The outcome is the room’s volume expressed in cubic meters (m³). A room with dimensions of 5 meters by 4 meters by 3 meters, for instance, has a volume of 5 meters by 4 meters by 3 meters, or 60 meters³. For an accurate determination of the heating requirements, this volume figure is essential.
The next step is to figure out how much each room will need to be heated after you have calculated its volume. A well-insulated room in a moderate climate should have 25–30 watts per cubic meter as a general guideline. However, this can change based on the environment, insulation, and the comfort level of the individual. The approximate wattage needed for each room can be calculated by multiplying its volume by the relevant watts per cubic meter. This calculation makes sure you have enough heating capacity to maintain a comfortable temperature in your house without using excessive energy.
Room Volume (m³) | Heating Capacity Needed (kW) |
50 – 100 | 4 – 8 |
100 – 150 | 8 – 12 |
150 – 200 | 12 – 16 |
200 – 250 | 16 – 20 |
250 – 300 | 20 – 24 |
- Calculation of the number of sections of heating radiators: by area and volume
- Calculation by the area of the room
- Accounting for additional parameters
- How to calculate the number of radiator sections
- Calculation by area
- We count the batteries in volume
- Heat transfer of one section
- Calculation of radiator sections depending on real conditions
- Calculation of the number of heating radiators by the area and volume of the room
- Calculation by area
- Calculation methodology for the volume of the room
- Correction of results
- Calculation of the number of radiator sections
- Dependence on the temperature regime of the heating system
- Calculation of the number of sections of heating radiators
- General recommendations for calculations and requirements
- How to calculate the number of sections of heating radiators for the room
- How to adjust the calculation results
Calculation of the number of sections of heating radiators: by area and volume
Determine the intended surface area of the heating device—that is, its size and number of sections—by calculating the volume or area of the room. Examples of such devices include radiators and pipe connection diagrams.
Because formulas consider a variety of parameters, you can obtain results with varying degrees of accuracy.
The necessary quantity of devices and their individual powers for residential properties.
Average standard values of the radiator section’s power derived from various materials:
- Steel- 110-150-
- Cast iron – 160 watts;
- Bimetallic – 180 watts;
- Aluminum – 200 watts.
It is possible to add more radiators to deaf cold walls; the number of devices typically matches the number of windows in the space.
Calculation by the area of the room
All calculations of the necessary heating device capacity are based on the most recent building standards:
For instance, the room’s area is 25 meters; multiply 25 by 100 (TU). It comes out to be 2.5 kW, or 2500 watts.
Steel radiators have a little power.
The resultant figure is divided by the power of one radiator model section, let’s say 150 watts.
Consequently, 2500 / 150 equals 16.7. After rounding, the result is 17. Therefore, 17 radiator sections will be needed to heat such a space.
If we are discussing areas like the kitchen that have more heat sources or little heat loss, rounding can be done less.
Since no other factors are taken into consideration, this calculation is extremely crude and rounded:
- The thickness and material of the walls of the building;
- Type of insulation and thickness of its layer;
- The number of external walls in the room;
- The number of windows in the room;
- The presence and type of double -glazed windows;
- Climate zone, temperature range.
Accounting for additional parameters
- 20%should be added to the result if the room has a balcony or bay window;
- If the room has two full -fledged window openings or two outer walls (angular arrangement), then 30% should be added to this resulting value.
- If it is planned to install decorative screens for radiators or a bundle, add another 10-15%.
- The installed high-quality double-glazed windows will allow you to take away 10-15% from the result.
- A decrease in the temperature of the coolant by 10 degrees (norm +70) will require an increase in the number of sections or capacity of the radiator by 18%.
- Features of the heating system-if the coolant is supplied through the lower hole, and exits through the upper one, then the radiator does not shorten about 7-10% of the power.
- In order to make some power supply, in case of atypical cooling and so on. It is customary to add 15% to the final result.
REPENTSIONS OF THE CLIMATIC AREAS
- For central Russia, the coefficient is not used (it is accepted for 1).
- For the northern and eastern regions, a coefficient of 1.6 is used.
- Southern regions 0.7-0.9, depending on minimal and average annual temperatures.
Therefore, you must multiply the thermal power result by the required coefficient in order to modify the climatic zone.
Formulas for figuring radiators based on volume or room area. High accuracy formula for a private residence. computation for the attic and loft, not
A room’s volume must be taken into consideration when calculating the amount of heating needed. You can choose and size the right heating system for a room by knowing its volume. Multiply the length, width, and height of the room to determine the heating by volume. The total volume is shown here in cubic feet or cubic meters. Usually, Volume is calculated as follows: Length × Width × Height. To ascertain the precise heating requirements, variables like window size, local climate, and insulation quality should be taken into account after the volume has been obtained. Accurate computation guarantees effective heating, minimizes energy wastage, and maintains year-round comfort in your house.
How to calculate the number of radiator sections
Radiators need to be replaced when updating the heating system, in addition to pipes. And now they come in a variety of sizes, shapes, and materials. They differ in the amount of heat that can be transferred to the air, which is equally significant. Additionally, this must always be considered when calculating the radiator’s sections.
If the amount of heat that escapes is balanced, the room will remain warm. As a result, the calculations are used to determine how much heat escapes the building (they rely on the climate zone, wall material, insulation, window area, etc.D.). One section’s thermal power is the second parameter. At the maximum system settings (90 °C at the input and 70 °C at the output), this is the maximum amount of heat it can produce. This feature, which is frequently seen on the package, must be mentioned in the passport.
With your help, we calculate how many heating radiator sections are needed, taking into account the characteristics of the building and the heating system.
One crucial thing to remember is that, when doing your own calculations, the majority of manufacturers state the highest amount they could have obtained in ideal circumstances. Thus, round up any amounts. When low-temperature heating occurs—that is, when the coolant at the entrance is warmer than 85 °C—thermal power searches for the appropriate parameters or performs a recalculation, as explained below.
Calculation by area
This is the most straightforward method for estimating how many sections are needed to heat the space. The norms for the average heating power of one square area are shown, based on numerous calculations. In order to account for the region’s climate, two norms were prescribed in SNIP:
- For the regions of the middle band of Russia, from 60 watts to 100 watts are required;
- For areas located above 60 °, the rate of heating per square meter is 150-200 W.
Why is there such a wide range provided in the norms? in order to account for the wall’s composition and level of insulation. The maximum values are used for concrete homes; the middle value can be used for brick homes. Minimal for homes with insulation. Another crucial point to note is that these norms are only calculated for average ceiling heights of 2.7 meters.
Formula for determining the number of radiator sections
Multiply the room’s area by its heat rate to find the setting that works best for you. Determine the room’s overall heat loss. Determine the thermal power of one section from the technical data for the chosen radiator model. Calculate their number by dividing the overall heat loss by power. It’s simple, but we provide an example to help clarify.
An illustration of how to divide the number of radiator sections by the room’s size
16 m 2 corner room in a brick house on the middle lane. Will install 140-watt thermal capacity batteries.
We consider heat loss in the middle of the range for a brick home. Given the angular nature of the room, it is best to take more. Decide on 95 watts. Then, it is discovered that 16 m 2 * 95 W = 1520 W is needed to heat the space.
We are now counting the quantity: 10.86 pieces, or 1520 W / 140 W. It comes out to be eleven pieces. There will be a great deal of radiator that needs to be installed.
The square’s heating battery calculation is straightforward but far from ideal because it makes no allowance for ceiling height. A different approach is taken when dealing with non-standard heights: in volume.
We count the batteries in volume
For the purpose of heating one cubic meter of space, there are standards in SNIP. They are provided for various kinds of buildings:
- For bricks per 1 m 3, 34 watts are required;
- for panel – 41 watts
This radiator section calculation is similar to the last one; the only differences are that volume and norms are taken into account instead of area. We divide the resultant number by the power of a single radiator section (cast iron, bimetallic, or aluminum) after multiplying the volume by the norm.
Formula for figuring out how many sections there are based on volume
An illustration of a volume calculation
For instance, we will figure out how many sections a 16 m 2 room with a 3 m ceiling height needs. The structure is made of brick. The same power is used by radiators: 140 W:
- We find the volume. 16 m 2 * 3 m = 48 m 3
- We count the required amount of heat (the norm for brick buildings 34 W). 48 m 3 * 34 W = 1632 W.
- We determine how many sections are needed. 1632 W / 140 W = 11.66 pcs. Round, we get 12 pcs.
You now know two methods for figuring out how many radiators a room has.
Heat transfer of one section
Radiators come in a wide variety these days. Even though most of them have similar exteriors, thermal indicators can vary greatly. They are contingent upon the material used in their construction, as well as the dimensions, wall thickness, internal section, and overall level of structural planning.
As a result, it is only possible to specify the precise number of kW in one section of an aluminum (cast iron bimetallic) radiator in relation to each model. The manufacturer has indicated these data. Ultimately, there is a noticeable disparity in size: some are low and deep, while others are tall and narrow. The Style 500 and Style Plus 500 tables below show that there can be a 15–25 watt difference in power between sections of the same height from different models made by the same manufacturer. Even more noticeable distinctions may exist between different manufacturers.
Specifications of certain bimetallic radiators. Please be aware that there may be a noticeable difference in thermal power between sections that are the same height.
However, the midpoint of each type of radiator’s heat capacity was determined in order to make an initial assessment of how many battery sections are required to heat the space. Approximate computations can be performed using them (data for batteries with an interax distance of 50 cm are provided):
- Bimetallic – one section selects 185 watts (0.185 kW).
- Aluminum – 190 watts (0.19 kW).
- Cast iron – 120 watts (0.120 kW).
More specifically, when you select a model and determine the dimensions, how many kW you can fit in one section of the bimetallic, aluminum, or cast-iron radiator. There can be a significant variance in cast-iron batteries. Their thermal power varies greatly because of their walls, which can be thin or thick. The average values for loved ones and regular-shaped (accordion) batteries are shown above. The "retro" style of thermal power uses radiators that are significantly smaller.
These are the technical specs for the Turkish manufacturer Demir Dokum’s cast-iron radiators. The distinction is not just noticeable. She has even greater potential.
These numbers, along with the average SNiP norms, indicate the average number of radiator sections per square meter.
- The bimetallic section will heat 1.8 m 2;
- aluminum-1.9-2.0 m 2;
- cast iron-1.4-1.5 m 2;
In light of these data, how many radiator sections are there? Even simpler. Divide the room’s area by the coefficient if you know it. For instance, the following will roughly be required for the heating of a 16 m 2 room:
- bimetallic 16 m 2 / 1.8 m 2 = 8.88 pcs, round – 9 pcs.
- aluminum 16 m 2 /2 m 2 = 8 pcs.
- cast iron 16 m 2 / 1.4 m 2 = 11.4 pcs, round – 12 pcs.
Please note that these calculations are only estimates. You can roughly estimate the costs of purchasing heating devices based on them. By selecting a model and counting the number of radiators based on the coolant temperature in your system, you can determine the exact number of radiators in the room.
Calculation of radiator sections depending on real conditions
We would like to remind you that one section of the battery’s thermal power is indicated under ideal circumstances. If the battery’s coolant is +90 °C at the entrance, +70 °C at the output, and the room is supported at +20 °C, then the battery will overheat. In other words, the system’s (also referred to as the "system") temperature pressure will be 70 ° C. What should you do if the temperature of your system at the case entrance is higher than +70 °C? or +23 °C is the minimum required room temperature? Determine the declared capacity again.
You must determine your heating system’s temperature pressure in order to accomplish this. For instance, the output temperature is +70 °C, the output temperature is 60 °C, and the required temperature in the room is +23 °C. We calculate your system’s delta, which is the arithmetic mean at the input and output less the ambient temperature.
The equation used to determine the heating system’s temperature and pressure
In our instance, the result is (70 °C + 60 °C)/2 – 23 °C = 42 °C. Delta in these circumstances is 42 °C. Next, we multiply the declared power by this coefficient, which we locate in the recalculation table (below). We impart the power that this section can provide for the circumstances you face.
Table of coefficients for various temperature deltas in heating systems
We find a line with a delta of 42 °C in blue-tinted columns. It is equivalent to a 0.51 coefficient. We now compute the radiator’s thermal power in the first section for our scenario. For instance, applying the discovered coefficient to the declared 185 watt capacity, we obtain 185 W * 0.51 = 94.35 W. Less than by nearly two times. Radiator section calculations require the substitution of this power. The only parameter in the room that will be considered individually is the temperature.
I really don’t want to install the outdated cast-iron "accordion" during the repair because there are more stylish radiators available. Since most radiators have a sectional structure, you will need to calculate the radiators’ sections in this situation.
Calculation of the number of heating radiators by the area and volume of the room
The question of how to figure out how many heating radiators and device sections there are in an apartment comes up when replacing the batteries or switching to individual heating. In the winter, the apartment will be cool if the batteries don’t have enough power. Not only can an excessive number of sections result in needless overpayments, but tenants occupying lower floors will be left without heat if the heating system has a single-pipe wiring. Based on the area or volume of the room, you can determine the ideal power and number of radiators while accounting for the characteristics of various battery types.
Calculation by area
The most popular and straightforward method is to divide the area of the heated room by the power of the devices needed for heating. The average norm states that 1 kV is needed for heating. 100 watts of thermal power are needed to cover one meter. Take a 15 kV-meter-square-area room as an example. This method indicates that 1,500 watts of thermal energy are needed to heat it.
When applying this method, there are a few key considerations to make:
- 100 watts per 1 sq. A meter of area belongs to the middle climatic strip, in the southern regions for heating 1 sq. Meter of the room requires lower power – from 60 to 90 watts;
- for areas with a harsh climate and very cold winter for heating 1 kV. meters required from 150 to 200 watts;
- The method is suitable for rooms with a standard ceiling height not exceeding 3 meters;
- The method does not take into account heat losses that will depend on the location of the apartment, the number of windows, the quality of insulation, the material of the walls.
Calculation methodology for the volume of the room
The calculation method that accounts for the volume of the ceiling will be more accurate because it considers the height of the apartment’s ceilings as well as the material used to make the exterior walls. The following is the calculation sequence:
- The volume of the room is determined, for this the area of the room is multiplied by the height of the ceiling. For a room of 15 square meters. m. and the height of the ceiling 2.7 m it will be 40.5 cubic meters.
- Different amounts of energy are spent depending on the material of the walls on heating of one cubic meter of air. According to SNiP standards for an apartment in a brick house, this indicator is 34 watts, for a panel house – 41 watts. So, the resulting volume must be multiplied by 34 or 41 watts. Then for a brick building for heating a room of 15 squares, 1377 W (40.5*34) will be required, for panel – 1660, 5 W (40.5*41).
Correction of results
If all the variables that influence the decrease or increase in heat loss are not taken into consideration, any of the chosen methods will only produce an approximative result. To ensure precision in the calculation, multiply the radiator power result by the coefficients listed below, selecting the appropriate one.
15–35% of the heat in the room may be lost through the windows, depending on their size and the quality of the insulation they provide. Thus, two coefficient windows will be used in the computations.
The proportion of the room’s floor to window area:
- for a window with a three -chamber double -glazed window or a two -chamber with an argon – 0.85;
- for a window with a conventional two -chamber double -glazed window – 1.0;
- for frames with ordinary double glazing – 1.27.
Ceiling and walls
The quantity of external walls, the standard of thermal insulation, and the room situated above the apartment all affect the amount of heat loss. There will be three additional coefficients used to adjust for these factors.
The quantity of exterior walls
- There are no external walls, heat losses are absent – a coefficient of 1.0;
- One outer wall – 1.1;
- two – 1.2;
- Three – 1.3.
- normal thermal insulation (wall with a thickness of 2 bricks or a layer of insulation) – 1.0;
- high degree of thermal insulation – 0.8;
- Low – 1.27.
Type of accounting for the room above:
- heated apartment – 0.8;
- heated attic – 0.9;
- Cold attic – 1.0.
If you calculated the area using a method for a room with a non-standard wall height, you will need to consider this in order to understand the outcome. The following is how to find the coefficient: The standard height, which is 2.7 meters, is separated from the current ceiling height. As a result, the following figures result:
The final coefficient accounts for the wintertime street air temperature. The average temperature during the coldest week of the year will serve as our starting point.
Calculation of the number of radiator sections
We can determine the amount of heating batteries once we know how much power is needed to heat the space.
You must divide the estimated total power by the power of a single device section in order to determine the number of radiator sections. The average indicators for various radiator types with a standard axial distance of 50 cm can be used for calculations:
- for cast -iron batteries, the approximate power of one section is 160 watts;
- for bimetallic – 180 watts;
- for aluminum – 200 watts.
Assistance: The height between the centers of the holes where the coolant is supplied and redirected is known as the radiator’s axial distance.
For instance, we figure out how many bimetallic radiator sections are needed in a 15 square meter space. Assume that you thought about power in the room in the most straightforward manner. Divide the 1,1800 watts needed for the 1,500 watts of heating. Wrap the resultant number 8.3; eight sections are needed for the bimetallic radiator.
Crucial! If you choose to use a non-standard battery, find out how much power one section of the device’s passport holds.
Dependence on the temperature regime of the heating system
Radiator power is recommended for systems with high heat regime temperatures. If your home’s heating system runs in a low-temperature thermal mode or a medium-trampressed mode, you’ll need to perform extra calculations to choose batteries with the right number of sections.
First, we calculate the system’s thermal pressure, which is the difference between the ambient temperature and the batteries. The average arithmetic temperature of the supply temperature and coolant removal is used to determine the temperature of the heating devices.
- High -temperature regime: 90/70/20 (feed temperature – 90 ° C, return – 70 ° C, a value of 20 ° C is accepted for the average temperature in the room). We calculate thermal pressure as follows: (90 + 70) / 2 – 20 = 60 ° C;
- Medium -compartment: 75/65/20, thermal pressure – 50 ° C.
- Low -temperature: 55/45/20, thermal pressure – 30 ° C.
The total power multiplied by the radiator passport pressure and the current thermal pressure divided will yield the number of battery sections required for systems with thermal pressures of 50 and 30. for a 15 kV.m. room. It is necessary to have 15 sections of aluminum radiators, 17 bimetallic sections, and 19 cast-iron battery sections.
You will require twice as many sections for a low-temperature heating system.
Computation of heating by area for various heating system configurations. Heat loss coefficients are used to correct the results.
Calculation of the number of sections of heating radiators
For every homeowner, accurately calculating the heating radiator sections is a crucial task. The room won’t warm up during winter colds if not enough sections are used, and the cost of buying and maintaining too-large radiators will be excessively high.
You can use the simplest calculations for standard rooms, but in order to get the most accurate result, it is occasionally necessary to account for various nuances.
General recommendations for calculations and requirements
Knowing certain parameters is necessary in order to perform calculations.
- The dimensions of the room that must be heated;
- Type of battery, material of its manufacture;
- The power of each section or whole battery depending on its type;
- The maximum allowable number of sections of the selected radiator model;
Radiators are separated into the following categories based on the material of manufacture:
- Steel. These radiators have thin walls and a very elegant design, but they are not popular due to numerous disadvantages. These include small heat capacity, rapid heating and cooling. With hydraulic strikes, a leak often occurs in places of joints, and cheap models quickly rust and work shortly for long. Usually whole, are not divided into sections, the power of steel batteries is indicated in the passport.
- Cast iron radiators are familiar to every person since childhood, this is the traditional material from which durable and have excellent technical characteristics of the battery is made. Each section of the cast -iron accordion of the Soviet era gave out a heat transfer of 160 watts. This is a prefabricated design, the number of sections in it is not limited. There can be both modern and vintage design. Cast iron holds heat perfectly, is not subject to corrosion, abrasive wear, compatible with any coolant.
- Aluminum batteries are easy, modern, have high heat transfer, thanks to their advantages they are becoming increasingly popular among buyers. The heat transfer of one section reaches 200 watts, they are produced by whole structures. Of the minuses, oxygen corrosion can be noted, but this problem is solved using anode metal oxidation.
- Bimetallic radiators consist of internal collectors and external heat exchanger. The inside is made of steel, and the external one is made of aluminum. High heat transfer rates, up to 200 watts, are combined with excellent wear resistance. The relative minus of these batteries is a high price compared to other types.
The characteristics of radiator materials vary, which has an impact on the calculations.
How to calculate the number of sections of heating radiators for the room
There are various methods for making calculations, and each one requires specific parameters.
On the room’s surface
The area of the room for which radiators are being purchased can be the focus of the initial computation. This is a very basic calculation that works well in rooms with 2.40–2.60 m ceilings. As per the construction standards, a room requiring heating will require 100 watts of thermal power per square meter.
We figure out how much heat the entire space will require. In order to accomplish this, we multiply the area by 100 watts, or 20 square meters, in this case. The computed thermal power for me will be 2 kW, or 2,000 watts (20 kV m*100 watts).
To ensure that there is enough heat in the house, heating radiator calculations must be done correctly.
This outcome needs to be split into the manufacturer-specified heat transfer of a single section. If it is 170 watts, for instance, the required number of radiator sections in our scenario would be: 2,000 W/170 W = 11.76, or 12, because the result needs to be rounded to the nearest whole number. Generally, rounding is done in the direction of increase; however, you can round the lesserway in rooms where heat loss is lower than average, like the kitchen.
Make sure you account for potential heat loss based on the particular circumstances. Naturally, heat loses more quickly in a room with a balcony or in a building that is positioned in a corner. In this instance, a 20% increase in the room’s computed thermal power value is necessary. If it is intended to mount the radiators in a niche or conceal them behind the screen, then the calculations should be increased by about 15% to 20%.
We have also created this calculator for you to make counting online more convenient:
If you compute the heating radiator sections by the room volume, for example, and account for the height of the ceiling, you will get more precise results. This case follows the same general principle as the preceding one. The total amount of heat required is determined first, followed by the number of radiator sections.
The room’s thermal energy requirement must be increased by 15% to 20% if the radiator is obscured by the screen.
41 watts of thermal power are required, per SNiP recommendations, to heat one cubic meter of living space in a panel house. We multiply the total volume by this normative value after multiplying the area of the room by the ceiling height. The amount of heat required in apartments with contemporary double-glazed windows and external insulation is reduced to 34 watts per cubic meter.
For instance, we determine how much heat is needed in a 20 square meter room with a ceiling height of three meters. The room will have a volume of sixty cubic meters (20 kV m * 3 m). In this instance, the computed thermal power will be 2,460 watts, or 60 cubic meters * 41 W.
How do you figure out how many heating radiators there are? Divide the data that was received into the heat transfer that one section’s manufacturer specified in order to accomplish this. If we use 170 watts, as in the previous example, then the room will require 2,460 W / 170 W = 14.47, or 15 radiator sections.
Producers make an effort to overstate the heat transfer indicators of their goods, implying that the coolant temperature in the system will reach its highest point. Since this requirement is rarely met in practice, you should concentrate on the product passport’s minimum indicators of one section’s heat transfer. As a result, the computations will be more precise and realistic.
If the space isn’t typical
Regretfully, not all apartments can be regarded as typical. Private residential structures are more affected by this. How can calculations be made that account for different operating conditions? Numerous variables will need to be considered in this.
The height of the ceiling, the quantity and size of windows, the existence of wall insulation, etc., must all be considered when determining the number of heating sections. P.
This method’s peculiarity lies in the fact that several coefficients are used to account for a room’s unique features that may have an impact on the amount of heat energy it can retain or produce.
This is how the calculation formula appears:
CT: the quantity of heat needed in a specific room;
P is the room’s square meters;
K1 is the coefficient that accounts for window opening glazing:
- for windows with ordinary double glazing – 1.27;
- for windows with double glass packet – 1.0;
- For windows with triple glass packet – 0.85.
K2 is the walls’ coefficient of thermal insulation:
- low degree of thermal insulation – 1.27;
- good thermal insulation (masonry in two bricks or a layer of insulation) – 1.0;
- High degree of thermal insulation – 0.85.
K3 is the proportion of the room’s floor to window area:
K4 is a coefficient that lets you account for the typical air temperature during the year’s coldest week:
- for -35 degrees -1.5;
- for -25 degrees -1.3;
- for -20 degrees -1.1;
- for -15 degrees -0.9;
- for -10 degrees -0.7.
K5 – modifies the requirement for heat by considering the quantity of exterior walls:
K6 – the type of room accounting, situated above:
- cold attic – 1.0;
- heated attic – 0.9;
- Heated housing – 0.8
K7 is the coefficient that accounts for ceiling height:
It is still necessary to round the result to the whole number and divide it by the heat transfer value of one radiator section.
How to adjust the calculation results
Heat losses must be taken into consideration when determining the number of sections. Heat can escape the house through the roof, windows, natural ventilation system, floor and basement, and walls and adjacent spaces.
Additionally, you can save money by insulating the sloping windows, doors, or loggia; you can also remove one or two sections of the heated towel rails and the kitchen slab to free up space for a radiator. Reduced heat loss and a smaller battery size can be achieved by using underfloor heating systems, fireplaces, and adequate wall and floor insulation.
When calculating, one must account for heat loss.
The number of sections may differ based on how the heating system is configured to operate, where the batteries are located, and how the system is connected to the heating circuit.
Private homes use autonomous heating, which is a more efficient system than centralized heating found in apartment buildings.
Heat transfer indicators are also impacted by how radiators are connected. When there is an overhead water supply, the diagonal method is thought to be the most cost-effective, while the lateral connection results in 22% loss.
The heating system’s schedule and the way radiators are connected may affect how many sections there are.
Corrections can also be made to the final result for single-pipe systems. When two-pipe radiators are supplied with a single temperature coolant, the one-pipe system functions in a different way, delivering cooled water to every section that follows. In this instance, the calculation is done initially for a two-pipe system, and then the number of sections is increased while accounting for thermal losses.
The single-pipe heating system’s calculation scheme is shown below.
The following sections receive cooled water in a single-pipe system:
If we have 15 kW at the entrance and 12 kW at the exit, then 3 kW is lost.
Losses in a room with six batteries will typically be 20%, meaning that two additional sections of the battery will be required. According to this calculation, the final battery should be enormous. To address the issue, shut-off valves are installed and connected via a bypass to modify the heat transfer.
Some manufacturers provide a quicker method for receiving a response. You can find a handy calculator made specifically for these calculations on their websites. To use the program, fill in the relevant fields with the required values. A precise result will then be displayed. You could also use a specialized program.
Nearly all the subtleties are included in this calculation of the number of heating radiators, which is predicated on a fairly precise definition of the requirements in terms of thermal energy.
Adjustments will ensure the heating system operates economically and efficiently for many years, save money on heating and unnecessary section purchases, and let you design a warm and inviting environment in your home or apartment.
The content was updated on March 29, 2018.
Methods for figuring out how many heating radiator sections a room needs. How to appropriately adjust while accounting for materials, heat loss, and other elements.
One of the most important things in making sure a living space is both comfortable and energy-efficient is figuring out how much heating a room actually needs. Homeowners can efficiently control their energy consumption and lower their heating expenses by figuring out the required heating capacity. Precise computations are necessary to keep a warm atmosphere throughout the winter without consuming unnecessary energy.
It is essential to comprehend the variables that influence heating computations. A number of variables are important, including the room’s size, the type of heating system, the local climate, and the quality of the insulation. By considering these variables, homeowners can choose the heating solutions that are best suited to their unique requirements.
To guarantee that the estimated heating requirements are precise and effective, proper insulation is essential. Good insulation keeps heat in the house, which lessens the strain on the heating system and, as a result, lowers energy costs. Insulation is an investment that pays for itself over time with lower energy bills and more comfort.
To guarantee the heating system’s longevity and efficiency, regular maintenance is required. Homeowners can optimize the system’s performance, reduce energy usage, and prevent unplanned malfunctions by maintaining it in good operating order. In the long run, a well-maintained system is more dependable and economical.
In conclusion, one of the most important steps in building a cozy and energy-efficient home is figuring out how much heat a room needs based on its volume. Homeowners can choose the best heating solutions by taking into account variables like room size, insulation, climate, and type of heating system. The best ways to cut energy use and guarantee long-term comfort and savings are to invest in adequate insulation and schedule routine heating system maintenance.