Adjustment of the temperature of water warm floors: how to correctly configure the control of heating, as well as the connection diagram to the thermostat?

Nothing beats the warmth of water-based underfloor heating systems for keeping our homes nice and comfortable. However, it’s crucial to know how to properly adjust the temperature if you want to take full advantage of this contemporary convenience. Correct configuration not only guarantees maximum comfort but also contributes to energy efficiency, ultimately saving you money.

Properly configuring the heating controls is crucial to attaining the ideal temperature on water-heated floors. This entails figuring out the ideal ratio to heat to energy use based on your tastes and way of life. Luckily, modifying these controls can be a simple task with the appropriate information and methodology.

The thermostat, which functions as the system’s brain, is essential to the management of water warm floors. Sustaining a comfortable indoor environment requires knowing how to connect and use it effectively. Modern thermostats come with a variety of features that let you customize your heating experience to meet your needs, from scheduling to remote temperature adjustments.

However, precisely how do you link the thermostat to your underfloor heating system? The direction required to make sure everything is configured correctly can be found in an understandable connection diagram. You can confidently configure your system for optimal performance by following the steps shown in the diagram.

Adjustment of temperature How to correctly configure the control of heating
Connection diagram How to connect to the thermostat

Why a comb is necessary

You ought to begin a narrative about the distribution comb by describing its function in the warm floor and explaining why the system’s regular operation cannot be guaranteed in its absence. The illustration below shows a simplified schematic of this type of heating. In the capacity of regular water, the coolant travels from the boiler (or, in the case of a city apartment, the centralized heating line) to a collector unit, where it is combined with a liquid that has previously circulated through the system. Subsequently, the water follows the shapes created beneath the floors, providing them with heat.

Diagram of a warm floor system that is simplified

The actual warm floor plan is typically more intricate than the one shown in the image above because it has multiple circuits with varying pipe lengths. They therefore require a distinct quantity of coolant. However, a lot of the hot water will rush into the smallest outline if it comes from a source like a boiler or a highway that has no distribution. There will be overheating as a result. On the other hand, the absence of heat will be noticeable on broader contours.

Diagram showing where the warm floor circuits are located in the house’s different rooms. You’ll see that their areas, as well as the locations of the supply and diverting lines, differ significantly.

Crucial! This issue is resolved by the presence of a properly adjusted comb, which establishes water consumption in each distinct area of the heated floor based on the coolant requirement. A large living room and a small bathroom will both heat up equally well at the same time.

Another purpose of the comb for a warm floor is to bring the water’s temperature down to a level suitable for contours. Coolant from the boiler and central line is supplied at temperatures between +70 and +80 degrees, or even higher, making any temperature below that unfavorable for fuel consumption. However, such a liquid is inappropriate for a heated floor. In order to cool it, it must mix with water that has already cooled from the "return" of heating contours. This takes place for a warm floor inside the comb. The collector uses linked valves and sensors to keep the temperature at a set point that the system user specifies.

Warm water floor Rowman Distribution (collector)

An eagle with a whip

Installation of the regulator: the need to use the device

The thermal attenter ensures that the warm floor will continue to operate without overheating or premature failure. Even though a water warm floor can function without a sensor (in the event that the project is not equipped), installing the equipment will alter the heating level, which you can see is quite helpful in specific seasonal weather movements. Furthermore, systems using liquid coolants are able to reach the appropriate temperature without relying on the coolant’s temperature range because the device controls the operation of a three-way valve or/and circulation pump.



Connection schemes

More often than not, a warm water floor serves as an extra heat source. It primarily connects to a shared hot water supply or heating system. The connection method determines the features of the warm floor adjustment.

There are multiple schematics showing how to connect water heating appliances.

Combined

A common and technically sound approach is combined heating, which combines a warm floor system with a radiator. But in order to arrange this design, we require:

  • boiler;
  • pump;
  • expansion tank;
  • collectors for radiators and warm floor;
  • radiators;
  • Pipes.

For various heating devices to function as intended, it is crucial that they be combined correctly. The following are the primary ways to integrate warm water floors and radiators into a single design:

  1. Parallel connection of the collector unit to the heating system. The contours of the highway to the batteries are cut. Fluid circulation is provided by the pump.
  2. Connection by rings, primary or secondary. The pipeline, when laying, forms rings, they crash into the supply system in several places. The temperature of the coolant depends on the removal of the serpentine from the heat source.
  3. Connecting to a compulsary manifold, to its extreme point. The water moves in the circuit due to the operation of the common house pump located in the generator. In this case, the warm floor has priority when serving hot coolant.
  4. With the use of a hydraulic distribution node – a great option: if there are several heating devices, with a difference in the length of the hinges of the floor and the flow of water in them. This scheme also can not do without a compliance collector.
  5. Local connection of the contour through the unibox according to a parallel scheme. Suitable for premises having a small area: bathroom, corridor.

Connection to the radiator

A typical method for heating floors with radiators. According to this plan, the radiator’s heating capacity directly affects the liquid’s temperature on the water floor.

Paul pipes, UNIBOKS, and a highway with a handling feed are required for the construction of this system. It is advised to connect the floor loops to the return because the water in the batteries can reach temperatures of up to 80 degrees.

This is a straightforward option because regulators are not required because the installed boiler is only intended to heat water for a warm floor.

All that’s needed to set the necessary indicator on the panel is for a modern gas boiler to be able to adjust the temperature on its own. The values for each device are easily adjustable to the boiler’s automation, even with a double-pin system when the boiler heats the floor and carries out water for the batteries.

The presence of a compensatory barrel is necessary when operating a solid fuel boiler. The installation of a pressure gauge, an air release valve, and a thermostat on the barrel of the security unit regulates the temperature and pressure.

Just so you know! The pipe laying scheme affects how well the water warm floor works; learn about the different types of styling schemes and how to connect warm floors. The heating caused by a "snake" will not be consistent, with hot and cold spots. Uniform heating is produced when the circuit is set up using the "Snail" scheme.

Preparatory work

Before connecting the temperature regulator, make sure you read the instructions that are attached to it. Since various manufacturers have different procedures, special attention should be paid to the part of the work where we are discussing how to install the sensor and how to carry out this work.

Initially, the front panel must be removed, and the control mechanism—which, on simpler models, takes the form of a wheel—must be carefully disassembled.

You must insert an element before unscrewing the screw holding the front panel to the mechanism in order to remove it with a screwdriver. The front panel of some models is held in place by unique plastic latches. Squeeze the latch with a screwdriver to remove it; it will click.

On the other hand, you shouldn’t use mechanical exposure to remove the panel if it cannot be removed. Ultimately, this makes it simple to break the latches, and replacing the regulator will take care of the issue. All you have to do to prevent this issue is carefully read the instructions and attempt to remove the panel once more, following the right procedure this time.

Purchasing the tools needed to install a warm floor thermostat is the next step.

A corrugated tube is the first item you should have. The sensor is typically included, but if the manufacturer is not listed for such a kit, it must be purchased separately.

The corrugation diameter of 16 mm is ideal. The height at which a temperature controller will be installed and the separation between the temperature sensor and the wall are important factors to consider when calculating the necessary corporate length. Moreover, you must measure the distance to the floor-mounted sensor from the height that a roulette indicates.

Temperature regime

Water warm flooring operates on a different principle than other types of heating equipment. the primary variation in the coolant’s temperature. For the water floor circuits, water is supplied to the radiators at a maximum temperature of 42 degrees, having been heated to 80 degrees. The floor will heat up to 26 degrees at this temperature.

The temperature of water warm floors can be changed using one of two methods:

  1. Carrying control at the collector supply node by mixing the spent water. This is achieved by equipment of a three -way valve with a thermostatic head. During operation, the temperature of water, not air, is taken into account, and the invariable volume of the fluid consumed is provided, with slight fluctuations in its temperature.
  2. Limiting the receipt of heated coolant into the pipes. This also requires a thermal head, it is placed on a three -way valve and is used to block the reverse flow. In this case, the feed and return taps are connected to the bypass, through it the flow is adjusted by the restrictive valve. Since warm floors are inert, water is supplied to the pipes with a nominal temperature, and only its consumption changes.

The thermostatic head in the work is repelled from the return temperature in both approaches.

Key safety provisions

Safety precautions should be strictly followed when performing any electrical work. The worst-case scenario is when these provisions are disregarded. The following are important suggestions:

  • Before starting work, de -energize the entire apartment/house or directly the line allocated to connect the thermostat, if such an opportunity is present;
  • Do not include a disassembled device in the mains;
  • Do not use the regulator at temperatures above +40 and below -5;
  • Do not allow dusting of the thermostat;
  • Do not use a variety of solvents for cleaning the device. The use of benzene for these purposes is also unacceptable;
  • Do not repair the regulator without the appropriate skills;
  • Do not allow exceeding power and current values above the manufacturer indicated in the instructions.


Setting up and adjusting water warm floor – instruction how to do the right thing

Nowadays, the majority of owners install water floors to improve the comfort of their homes during the colder months. However, it turns out that a pleasant microclimate in the apartment is not always achieved, even with the right system design and installation.

The heating system’s improper adjustment is the cause. As a result, knowing how to properly set up a water warm floor is crucial.

Just so you know! Additionally, personalized heating structures allow you to easily and affordably customize the ideal degree of heat.

Optimum temperature parameters

Depending on each person’s needs, the water warm floor is adjusted. Even in the worst frosts, some people prefer the refreshing freshness of a warm room, while others love the warmth of the space. However, sanitary standards were taken into consideration when developing certain general standards, which include:

  • heating the floor to 28 degrees;
  • In the presence of another heat source or when living in the room constantly, the ideal level from 22 to 26 is the optimal conditions for a person;
  • If this type of heat source is the only one, or it is in the bathroom, the corridor, on the balcony, or in a house where they do not constantly live, it is permissible to raise a degree

Thus, these norms should be considered when controlling water floors in addition to its preferences to ensure a healthy microclimate in the apartment.

Connection schemes

More often than not, a warm water floor serves as an extra heat source. It primarily connects to a shared hot water supply or heating system. The connection method determines the features of the warm floor adjustment.

There are multiple schematics showing how to connect water heating appliances.

Combined

A common and technically sound approach is combined heating, which combines a warm floor system with a radiator. But in order to arrange this design, we require:

  • boiler;
  • pump;
  • expansion tank;
  • collectors for radiators and warm floor;
  • radiators;
  • Pipes.

For various heating devices to function as intended, it is crucial that they be combined correctly. The following are the primary ways to integrate warm water floors and radiators into a single design:

  1. Parallel connection of the collector unit to the heating system. The contours of the highway to the batteries are cut. Fluid circulation is provided by the pump.
  2. Connection by rings, primary or secondary. The pipeline, when laying, forms rings, they crash into the supply system in several places. The temperature of the coolant depends on the removal of the serpentine from the heat source.
  3. Connecting to a compulsary manifold, to its extreme point. The water moves in the circuit due to the operation of the common house pump located in the generator. In this case, the warm floor has priority when serving hot coolant.
  4. With the use of a hydraulic distribution node – a great option: if there are several heating devices, with a difference in the length of the hinges of the floor and the flow of water in them. This scheme also can not do without a compliance collector.
  5. Local connection of the contour through the unibox according to a parallel scheme. Suitable for premises having a small area: bathroom, corridor.

Connection to the radiator

A typical method for heating floors with radiators. According to this plan, the radiator’s heating capacity directly affects the liquid’s temperature on the water floor.

Paul pipes, UNIBOKS, and a highway with a handling feed are required for the construction of this system. It is advised to connect the floor loops to the return because the water in the batteries can reach temperatures of up to 80 degrees.

This is a straightforward option because regulators are not required because the installed boiler is only intended to heat water for a warm floor.

All that’s needed to set the necessary indicator on the panel is for a modern gas boiler to be able to adjust the temperature on its own. The values for each device are easily adjustable to the boiler’s automation, even with a double-pin system when the boiler heats the floor and carries out water for the batteries.

The presence of a compensatory barrel is necessary when operating a solid fuel boiler. The installation of a pressure gauge, an air release valve, and a thermostat on the barrel of the security unit regulates the temperature and pressure.

Just so you know! The pipe laying scheme affects how well the water warm floor works; learn about the different types of styling schemes and how to connect warm floors. The heating caused by a "snake" will not be consistent, with hot and cold spots. Uniform heating is produced when the circuit is set up using the "Snail" scheme.

Temperature regime

Water warm flooring operates on a different principle than other types of heating equipment. the primary variation in the coolant’s temperature. For the water floor circuits, water is supplied to the radiators at a maximum temperature of 42 degrees, having been heated to 80 degrees. The floor will heat up to 26 degrees at this temperature.

The temperature of water warm floors can be changed using one of two methods:

  1. Carrying control at the collector supply node by mixing the spent water. This is achieved by equipment of a three -way valve with a thermostatic head. During operation, the temperature of water, not air, is taken into account, and the invariable volume of the fluid consumed is provided, with slight fluctuations in its temperature.
  2. Limiting the receipt of heated coolant into the pipes. This also requires a thermal head, it is placed on a three -way valve and is used to block the reverse flow. In this case, the feed and return taps are connected to the bypass, through it the flow is adjusted by the restrictive valve. Since warm floors are inert, water is supplied to the pipes with a nominal temperature, and only its consumption changes.

The thermostatic head in the work is repelled from the return temperature in both approaches.

System refueling rules

If the liquid in the pipeline changes by itself, it will be impossible to properly configure the water structure to function. If there is air in the system, this may occur; refer to the instructions for lowering the air from the heated floor on your own. As a result, it’s critical to properly correct the design as well as mount it professionally.

Automatic air vents should be installed in both collector branches of the system to ensure high-quality filling. It is recommended that floor loop refueling be done independently of other heating devices. The radiators and generator are pre-filled. The collector entrance valves overlap prior to refueling.

The air hose must be connected to the return and the hose from the water supply or pump to the supply cranes in order for the floor to start correctly.

It is essential to begin adding the collector and its distribution nodes to the water floor. In order to accomplish this, turn off the return taps at the same time that the supply valve’s flowers fully open.

The hinges fill in turn, the water comes from the painting hose, it’s not clear, and there are no air bubbles in it. A little pressure should be applied to the launch water to ensure more uniform air extraction from the pipes. The device can be included once all of the loops have been refueled.

Collaborating with gatherers

Establishing the norms for every loop is necessary to maintain the warm floor’s equilibrium. In fact, the amount of water needed varies depending on the size of the floor branch, allowing the coolant to cool in accordance with the calculated value as it passes through it. The heat load on the liquid that the loop passes through is equal to its volume.

Frequently, it is advised to calculate the coolant flow rate by dividing the volume of the incoming fluid by the loop length, which is equivalent to dividing the pump’s power. Nonetheless, it is worthwhile to give up on this approach because it makes figuring out the diameter of each coil difficult.

Furthermore, using this method of calculation results in pressure in the loops that is inconsistent with the calculated value, which prevents the structure from being configured.

The actual consumables adjustment procedure is straightforward and consists of an article with detailed instructions. Depending on the model, the device’s capacity can be changed by rotating the housing or a rod that can be unlocked with a key. Only the desired value needs to be set, and the device will display the volume of water in liters that has elapsed in a minute.

Basically, whenever one loop’s throughput is changed, the others also change. For this reason, each flowmeter should go through the procedure one after the other. Severe malfunctions suggest that either the circulating pump is not performing well or the reinforcement has a low throughput.

Ways to adjust the temperature of the heating floors

You must configure the device in order to obtain the necessary temperature values that adhere to accepted standards.

It is possible to properly adjust the heating water floors when the type of room is taken into consideration. The ideal temperature range for residential buildings is between 20 and 28 degrees. The ideal temperature range for the kitchen, hallway, or bathroom is between 19 and 24 degrees.

Just so you know! Although a room’s relative humidity of 60% is allowed, an indicator between 40% and 50% is thought to be ideal.

Maintaining a consistent temperature differential between the input and output is the primary objective of adjustment. The thickness and composition of the screed, as well as the sequential placement of the pipes, are considered in order to ascertain the temperature differential.

The design techniques have an impact on the installed equipment, which is mechanical and automated. The water consumption device is adjusted; this can be achieved through restriction or by combining hot and cooled coolant.

Automatic adjustment

The RTL thermal head or the unique valve are the primary components of the settings if the warm floor adjustment is done automatically. The established indicator determines how much heat is applied to the floor; the larger the indicator, the more hot fluid passes through the pipes and warms the sexual coating more intensely.

There are two methods for automatically adjusting a water warm floor:

  1. Using a thermostatic self -regulating device, in it the setting is made by valves or a crane with heads.
  2. Using an electronic system, it includes an electrothermometer, controller, electric drives.

Although electronic regulatory devices are costly, you can program and set up the floor heating system with their assistance to ensure optimal and efficient performance.

Numerous companies are present in the market as electronic regulators; the most well-known being NUNROTA.

Manual temperature alignment

The manual settling process is quick but takes a while. By opening or closing the valves, the temperature of the water heating can be adjusted. When a device is present that doses the supply to each branch, the process becomes much simpler.

Just so you know! Floor heating will work well on the manual setting; a separate heat pump can be used to accomplish this with vigorous water circulation in the pipeline.

Make sure there are no air traffic jams in the system and that it is full of air before attempting to adjust the water floor’s temperature. The coolant supply and flow rate level settings are made for each coil. At the input and output, control is applied while accounting for the variation in flow temperature. This process needs to be done once a year.

Crucial! All loops should have coolant entering them at roughly the same temperature, with a 5 to 15 degree variance allowed.

The use of the thermometer, laser, or electric will be made easier with control over the water floor’s adjustment process. The setting time will be greatly shortened by its presence.

Hydraulic alignment of the system

The warm water floor design is dependable and secure. But the right setup is needed to make it look that way. The best way to control warm floor water in a private home is to install a collector group with expenses and a working pressure of six bars. This power is insufficient if central heating is installed in the home.

If the collector has servo drives, the water consumption is automatically changed as needed. Preliminary setting will still need to be completed, though. You cannot function at all without such an adjustment in the absence of this drive.

The following formula can be used to determine the coolant flow rate:

Q/(1,*ΔT) = GUD, where

  • GUD – a specific volume of water on M2;
  • Q is the floor power;
  • Δt – the difference in the temperature of the coolant during supply and output;
  • 1, – the correction factor.

The specific consumption of the surface area should be multiplied in the future to determine the volume of liquid that flows through the loop.

Hydro-leveling is the simplest solution to implement:

  • calculate the volume of water for each loop, by multiplying the floor area, where this circuit is laid by 8.6 (average value);
  • run the pump at the first speed;
  • install a thermal tank at 30 degrees;
  • Check that the liquid is freely passing through the loops, and all the air came out;
  • Configure the consumption device on each circuit so that the value is equal to the water consumption that you calculated.

The actions that are indicated are intended; that is, more adjustments will be needed as the warm floor operates, taking individual comfort preferences into consideration.

The capabilities of the three -way valve

If the comb has a three-way valve, a servo drive is used for tuning. In this instance, a mixing valve will be operated by indicator control. A three-way valve can be turned as much or as little as desired during this process. However, it is more challenging to manufacture the mixing valve’s configuration.

Why is a comb necessary for a warm floor? Examine its components and working principle; learn how to select one; and find step-by-step installation and configuration instructions complete with pictures and videos.

Using a modular mixer provides an additional way to modify the heating of the floors. It entails:

  • three -way crane;
  • thermometer;
  • bypas;
  • pump for liquid circulation;
  • thermostatic head;
  • relay.

Although this set is expensive, it is very effective. The European assembly is a prerequisite for this module to operate.

A thermostat and servo drive are installed as an additional means of controlling the heated floors. When the room temperature drops and the heated coolant needs to be fed, the thermostat sounds the alarm for a servo drive. This process works even if you put together a collector by hand.

A warm water floor is a complicated structure, so before you decide to install one in your home, you should understand that you must regularly adjust the system in accordance with the instructions—mounting the system alone is not enough. And it’s critical to comprehend this procedure; otherwise, the floor may fall short of your expectations.

Video instructions

Water warm floor: composition and modification.

System refueling rules

If the liquid in the pipeline changes by itself, it will be impossible to properly configure the water structure to function. If there is air in the system, this may occur; refer to the instructions for lowering the air from the heated floor on your own. As a result, it’s critical to properly correct the design as well as mount it professionally.

Automatic air vents should be installed in both collector branches of the system to ensure high-quality filling. It is recommended that floor loop refueling be done independently of other heating devices. The radiators and generator are pre-filled. The collector entrance valves overlap prior to refueling.

The air hose must be connected to the return and the hose from the water supply or pump to the supply cranes in order for the floor to start correctly.

It is essential to begin adding the collector and its distribution nodes to the water floor. In order to accomplish this, turn off the return taps at the same time that the supply valve’s flowers fully open.

The hinges fill in turn, the water comes from the painting hose, it’s not clear, and there are no air bubbles in it. A little pressure should be applied to the launch water to ensure more uniform air extraction from the pipes. The device can be included once all of the loops have been refueled.

Collaborating with gatherers

Establishing the norms for every loop is necessary to maintain the warm floor’s equilibrium. In fact, the amount of water needed varies depending on the size of the floor branch, allowing the coolant to cool in accordance with the calculated value as it passes through it. The heat load on the liquid that the loop passes through is equal to its volume.

Frequently, it is advised to calculate the coolant flow rate by dividing the volume of the incoming fluid by the loop length, which is equivalent to dividing the pump’s power. Nonetheless, it is worthwhile to give up on this approach because it makes figuring out the diameter of each coil difficult.

Furthermore, using this method of calculation results in pressure in the loops that is inconsistent with the calculated value, which prevents the structure from being configured.

The actual consumables adjustment procedure is straightforward and consists of an article with detailed instructions. Depending on the model, the device’s capacity can be changed by rotating the housing or a rod that can be unlocked with a key. Only the desired value needs to be set, and the device will display the volume of water in liters that has elapsed in a minute.

Basically, whenever one loop’s throughput is changed, the others also change. For this reason, each flowmeter should go through the procedure one after the other. Severe malfunctions suggest that either the circulating pump is not performing well or the reinforcement has a low throughput.

Ways to adjust the temperature of the heating floors

You must configure the device in order to obtain the necessary temperature values that adhere to accepted standards.

It is possible to properly adjust the heating water floors when the type of room is taken into consideration. The ideal temperature range for residential buildings is between 20 and 28 degrees. The ideal temperature range for the kitchen, hallway, or bathroom is between 19 and 24 degrees.

Just so you know! Although a room’s relative humidity of 60% is allowed, an indicator between 40% and 50% is thought to be ideal.

Maintaining a consistent temperature differential between the input and output is the primary objective of adjustment. The thickness and composition of the screed, as well as the sequential placement of the pipes, are considered in order to ascertain the temperature differential.

The design techniques have an impact on the installed equipment, which is mechanical and automated. The water consumption device is adjusted; this can be achieved through restriction or by combining hot and cooled coolant.

Automatic adjustment

The RTL thermal head or the unique valve are the primary components of the settings if the warm floor adjustment is done automatically. The established indicator determines how much heat is applied to the floor; the larger the indicator, the more hot fluid passes through the pipes and warms the sexual coating more intensely.

There are two methods for automatically adjusting a water warm floor:

  1. Using a thermostatic self -regulating device, in it the setting is made by valves or a crane with heads.
  2. Using an electronic system, it includes an electrothermometer, controller, electric drives.

Although electronic regulatory devices are costly, you can program and set up the floor heating system with their assistance to ensure optimal and efficient performance.

Numerous companies are present in the market as electronic regulators; the most well-known being NUNROTA.

Manual temperature alignment

The manual settling process is quick but takes a while. By opening or closing the valves, the temperature of the water heating can be adjusted. When a device is present that doses the supply to each branch, the process becomes much simpler.

Just so you know! Floor heating will work well on the manual setting; a separate heat pump can be used to accomplish this with vigorous water circulation in the pipeline.

Make sure there are no air traffic jams in the system and that it is full of air before attempting to adjust the water floor’s temperature. The coolant supply and flow rate level settings are made for each coil. At the input and output, control is applied while accounting for the variation in flow temperature. This process needs to be done once a year.

Crucial! All loops should have coolant entering them at roughly the same temperature, with a 5 to 15 degree variance allowed.

The use of the thermometer, laser, or electric will be made easier with control over the water floor’s adjustment process. The setting time will be greatly shortened by its presence.

This article covers how to properly set up heating controls and connect them to the thermostat, as well as the critical topic of regulating the temperature of water warm floors. Maintaining comfort and energy efficiency in your home requires properly configured heating controls. We’ll walk you through each step of the procedure to make sure you know how to get the most out of your warm floor system. We cover everything you need to know to keep your home comfortable and effective throughout the seasons, from setting thermostats to understanding thermostat wiring diagrams.

Criterias of choice

The flow meter model influences the room in the room and the proper operation of the system in many ways. As a result, careful consideration should go into its decision.

Also see: Technoplex, foam, foam, and foam comparison

If you’re purchasing a roteter for a heated floor, you should consider:

  1. The material from which the case is made. Brass – has high wear resistance, and on top such a device is covered with nickel. Such a product is expensive. Plastic – affordable at a price, but its strength is below below.
  2. Integrity – before buying the product, you need to inspect the case and the flask for the presence of cracks and defects.
  3. The inner spring should be steel.
  4. Flask. In quality products, it is polycarbonate. This material has increased heat resistance and fortress.
  5. Technical indicators – they can be found in the instructions. A temperature of at least 110 degrees, and pressure – 10 bar.
  6. Passing capacity – at least 2 – 4 m3 of water should pass through a rotameter.
  7. The reliability of the manufacturer is the obligatory availability of a quality certificate for the product and the warranty period of at least 5 years. Not conscientious manufacturers, in order to make a profit, try to replace expensive and high -quality elements of the device with less high -quality.

By following these suggestions, you can buy a high-quality device from the stores, which have a large selection of these devices.



Hydraulic alignment of the system

The warm water floor design is dependable and secure. But the right setup is needed to make it look that way. The best way to control warm floor water in a private home is to install a collector group with expenses and a working pressure of six bars. This power is insufficient if central heating is installed in the home.

If the collector has servo drives, the water consumption is automatically changed as needed. Preliminary setting will still need to be completed, though. You cannot function at all without such an adjustment in the absence of this drive.

The following formula can be used to determine the coolant flow rate:

GUD is equal to Q/(1.163*ΔT).

  • GUD – a specific volume of water on M2;
  • Q is the floor power;
  • Δt – the difference in the temperature of the coolant during supply and output;
  • 1,163 – correction coefficient.

The specific consumption of the surface area should be multiplied in the future to determine the volume of liquid that flows through the loop.

Hydro-leveling is the simplest solution to implement:

  • calculate the volume of water for each loop, by multiplying the floor area, where this circuit is laid by 8.6 (average value);
  • run the pump at the first speed;
  • install a thermal tank at 30 degrees;
  • Check that the liquid is freely passing through the loops, and all the air came out;
  • Configure the consumption device on each circuit so that the value is equal to the water consumption that you calculated.

The actions that are indicated are intended; that is, more adjustments will be needed as the warm floor operates, taking individual comfort preferences into consideration.



A comfortable and energy-efficient home depends on the water-based underfloor heating systems’ temperature being adjusted. You can make sure that your floors are warm when needed without wasting energy or overheating the room by properly configuring the heating controls.

The thermostat, which serves as the heating system’s brain, is a crucial part of this procedure. To get exact temperature control, the thermostat must be connected correctly. By controlling the hot water flow via the underfloor pipes, the thermostat works in tandem with the heating system to maintain the desired temperature.

It’s crucial to take into account elements like your home’s layout, insulation quality, and each room’s heating needs when configuring the thermostat. Zoning your underfloor heating system can help maximize energy use and guarantee comfort throughout your house because different areas may have different heating needs.

Comprehending the thermostat’s connection diagram is imperative for an accurate installation. The thermostat will usually have connections to a power source and the heating system. To guarantee a secure and efficient setup, carefully follow the manufacturer’s instructions.

Your underfloor heating system can operate at peak efficiency and help detect problems early with routine maintenance and periodic checks. Maintaining a more comfortable living space and reducing energy use can also be achieved by keeping an eye on the temperature settings and making necessary adjustments.

In conclusion, you can maximize the performance of your water-based underfloor heating system by properly configuring the temperature controls and comprehending the thermostat connection diagram. You can reap the long-term advantages of comfortable, energy-efficient heating in your house with proper installation and upkeep.

Video on the topic

Indoor thermostat is controlled by a warm floor and radiators

Water -floor thermoregulator. HOW IT WORKS

Thermoregulator scheme. We connect correctly! Valtec. Service management

Zonal heating control or warm floor through servo drives and indoor thermostats

What type of heating you would like to have in your home?
Share to friends
Anna Vasilieva
Rate author
vDomTeplo.com
Add a comment